Range name | TeSys D |
Main function | Contactor (DOL) |
Rated Voltage (AC) - Phase-to-phase | 690 V |
Control Voltage (AC) | (50/60Hz) 220 Vac |
Rated current | (Un<= 440Vac) 25 A |
| (Un<440Vac AC-3) 25 A |
| (Un<440Vac AC-1) 40 A |
Rated active power (P) | (380-400Vac AC-3) 11 kW |
| (500Vac AC-3) 15 kW |
| (660-690Vac AC-3) 15 kW |
| (220-230Vac AC-3) 5.5 kW |
| (415 to 440Vac AC-3) 11 kW |
| (415Vac) 11 kW |
Poles | 3 Pole(s) |
Number of Normally Open (NO) circuits | 3 NO Pole(s) |
Application type | DOL (Direct On Line) |
Normally Open (NO) auxliary contacts | 1 NO contacts |
Normally Closed (NC) auxiliary contacts | 1 NC contacts |
Compliant with standard(s) | IEC60947-4-1 |
| IEC60947-5-1 |
| UL 508 |
| CSA C22.2 No 14 |
Electrical durability (with load) | (440VAC AC-3) 1 650 000 operations |
| (440VAC AC-1) 1 400 000 operations |
Mechanical durability (at no load) | 15 000 000 operations |
Connection type | Screw-type terminal |
Net Height | 85 mm |
Net Width | 45 mm |
Net Depth | 92 mm |
Net weight | 0.37 g |
Primary brand | Schneider Electric |
Secondary brand | Telemecanique |