range of product | EasyPact | |
---|
product or component type | Circuit breaker | |
---|
device short name | Easypact EZC100F | |
---|
circuit breaker name | Easypact EZC100F | |
---|
device application | Distribution | |
---|
poles description | 3P | |
---|
protected poles description | 3t | |
---|
network type | AC DC | |
---|
network frequency | 50/60 Hz | |
---|
[In] rated current | 100 A at 40 °C | |
---|
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
---|
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 | |
---|
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2 | |
---|
breaking capacity code | F | |
---|
breaking capacity | 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
---|
[Ics] rated service breaking capacity | 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
---|
suitability for isolation | Yes conforming to IEC 60947-2 | |
---|
utilisation category | Category A | |
---|
trip unit name | TM-D | |
---|
trip unit technology | Thermal-magnetic | |
---|
trip unit rating | 15 A at 50 °C | |
---|
protection type | Short-circuit protection Overload protection | |
---|
pollution degree | 3 conforming to IEC 60664-1 3 conforming to IEC 947-1 |
---|